YAOZE SKM-12 modular circuit breaker mechanism assembly for 12kV systems: a spring operating mechanism with independent frame design, available as a fixed installation unit or as a draw-out unit with a withdrawable truck. Mechanical life ≥ 30,000 operations, rated current up to 4000A, rated short-circuit breaking current up to 40kA.

Modular mechanism

Circuit breaker frame

SKM-12 • 12kV modular circuit breaker mechanism assembly

SKM-12 spring operating mechanism

Product Overview

The spring operating mechanism adopts an independent design from the frame. It can be used either as a fixed installation unit or assembled with a withdrawable truck to form a draw-out unit. It features long service life, simple maintenance, no pollution, no explosion risk, and low noise, and is suitable for harsh working conditions such as frequent operations.

Product Features

  • The spring operating mechanism adopts an innovative modular design.
  • Optional phase spacing and pole spacing to meet various special requirements.
  • Stable mechanical and electrical performance, high reliability, with a mechanical life ≥ 30,000 operations.
  • The operating mechanism can be equipped with an online monitoring system for mechanical characteristics.

Model Composition And Meaning

SKM 1 - 12 - □ / □ model code

Dimensions

Dimensions of the SKM-12 circuit breaker mechanism

Outline of CB Mechanism (650/800/1000 mm)

Outline of CB mechanism 650/800/1000mm

Mounting Outline for 650/800mm CB Frame

Mounting outline for 650/800mm CB frame

Mounting Outline for 1000mm CB Frame

Mounting outline for 1000mm CB frame

Selection Table

Circuit breaker frame, modular mechanism and cradle

Model Image Cabinet Width Model
Modular Mechanism 650mm
800mm
SKM1-JG-800
1000mm SKM1-JG-1000
Circuit Breaker Frame 650mm
800mm
1000mm
SKM1-KJ-650
SKM1-KJ-800
SKM1-KJ-1000
800mm

Circuit Breaker Assembly (without Poles)

SKM-12 circuit breaker assembly without poles

Main Parameters of Closing and Opening Electromagnets and Related Electrical Components

Item Closing Solenoid Opening Solenoid Interlocking Solenoid Anti-pumping Relay
Rated Op. Voltage (V) DC220 DC110 DC220 DC110 DC220 DC110 DC220 DC110
Rated Op. Current (A) 1.1 2.2 1.1 2.2 25mA 9.1mA
Rated Power (W) 242 242 242 242 2.7 1
Operating Voltage Range 85% -100%
Rated Voltage
65% – 120% Un open;
<30% Un no open.

Technical Parameters of the Energy Storage Motor

Model Rated V. Rated Power Operating Voltage Range Energy Storage Time
64ZY-CJ □ □ -6B-1 DC110V
DC220V
90W 85% -110% ≤ 10S

Main Technical Parameters

Item Unit Parameters
Rated Voltage kV 12
Maximum Operating Voltage kV 12
Rated Current A 630 630 1250 1600
1250 1250 1600 2000
2000 2500
2500 3150
4000
Rated Short-circuit Breaking Current kA 20 25 31.5 40
Rated Short-circuit Making Current kA 50 63 80 100
Rated Peak Withstand Current kA 50 63 80 100
Rated Short-time Withstand Current (4 s) kA 20 25 31.5 40
Rated Insulation
Level
Power Frequency Withstand Voltage (Before/After Rated Breaking) kA 42(Contact Gap48)
Impulse Withstand Voltage (Before/After Rated Breaking) 75(Contact Gap 85)
Rated Operating Sequence 0-0.3s-CO-180s-CO
Mechanical Life Times 20000
Number of Breaks at Rated Short-Circuit Current Times 50
Operating Mechanism Rated Closing Voltage (DC) V 110,220
Operating Mechanism Rated Opening Voltage (DC) V 110,220
Contact Gap mm 9±1
Contact Travel mm 3.5±0.5
Contact Bounce Time on Closing ms ≤ 2
Phase-to-Phase Asynchronous Opening/Closing mm ≤ 2
Opening Time ms ≤ 50
Closing Time ms ≤ 100
Average Opening Speed m/s 1.1±0.2
Average Closing Speed m/s 0.6±0.2
Contact Pressure N 20kA 25kA 31.5kA 40kA
2000 2400 3200 4750
Main Circuit Resistance per Phase uΩ 60 50

SKM-12 Electrical Schematic Diagram of Vacuum Circuit Breaker

SKM-12 electrical schematic diagram